Code No.B1061: Air outlet damper potentio.high
Code No.B1062: Air outlet damper potentio.low




DIAGNOSIS CODE SET CONDITION


This code is set when the mode selection damper control motor potentiometer does not send any signal to the A/C-ECU due to short or open circuit.

POSSIBLE CAUSES



  • Malfunction of the mode selection damper control motor and potentiometer
  • Damaged the wiring harness or connectors
  • Malfunction of the auto A/C controller assembly (A/C-ECU).

DIAGNOSIS PROCEDURE


STEP 1. M.U.T.-III data list


Check that the following service data display contents are normal.
Item No.55: Air outlet c/o potentiometer
Item No.56: Air outlet c/o potentio.(Target)

Q. Is the check result normal?

Go to Step 3.
Go to Step 2.

STEP 2. Check open and short circuit in SENB, MODP and SENG line between mode selection damper control motor and potentiometer connector (potentiometer side) and auto A/C controller assembly (A/C-ECU) connector.


Q. Is the check result normal?

Go to Step 4.
Repair the connector(s) or wiring harness.

STEP 3. Check the mode selection damper control motor and potentiometer.


Refer to .

Q. Is the check result normal?

Go to Step 4.
Replace the mode selection damper control motor and potentiometer.

STEP 4. Check whether the diagnosis code is reset.


Q. Is the diagnosis code set?

Replace the auto A/C controller assembly (A/C-ECU).
The trouble can be an intermittent malfunction (Refer to GROUP 00, How to Cope with Intermittent Malfunction ).